Heat Loss Calculator

Estimate a home's heat loss on a cold day and the furnace or boiler size it needs.

About the Heat Loss Calculator

Heat escapes through walls, windows, roof and floor in proportion to their area, their U-value (how easily heat passes through) and the indoor–outdoor temperature difference, plus heat carried away by air leaking in. This simplified whole-house estimate models the home as a box with typical U-values for its insulation level. Oversized furnaces cycle on and off and waste energy, so a proper load calculation is worth doing.

The formula

Q = Σ U × A × ΔT + 0.33 × ACH × volume × ΔT (W, with U in W/m²K and volume in m³)

U-values used (W/m²K) and air changes per hour

LevelWallsRoofFloorWindowsACH
Poorly insulated (older, single glazing)1.510.84.81.5
Average (some insulation, double glazing)0.60.30.52.80.8
Well insulated (modern code)0.280.150.251.40.5
Very high performance0.150.10.150.80.3

Worked example

Example: Design heat loss = 54,807 BTU/h (16.1 kW)

  1. Inputs: Heated floor area: 2,200; Area in: ft²; Storeys: 2; Ceiling height: 2.8 m; Insulation level: Average (some insulation, double glazing); Windows as % of wall area: 17%; Indoor temperature: 77; Outdoor design temperature: 11; Temperatures in: °F; Furnace / boiler efficiency (AFUE): 100%.
  2. Formula: Q = Σ U × A × ΔT + 0.33 × ACH × volume × ΔT (W, with U in W/m²K and volume in m³)
  3. Result: Design heat loss = 54,807 BTU/h (16.1 kW)

Things to keep in mind

  • An estimate for budgeting; size equipment from a professional room-by-room load calculation.

Questions people ask

What's a design temperature?

A cold-day temperature exceeded 99% of the year in your area; local building codes list it.

Why include air leakage?

In older homes, draughts can be a third of the heat loss.