Wire Size Calculator
Choose the smallest wire gauge that keeps voltage drop within your limit for a load and length.
About the Wire Size Calculator
Two things size a cable: it must carry the current without overheating (ampacity, which depends on insulation and installation method) and it must keep voltage drop acceptable. This picks the smallest size meeting your drop limit and, for US copper, the NEC 75 °C ampacity.
The formula
Smallest size with 2 I R L ÷ V ≤ limit (and ampacity ≥ I)
Worked example
Example: Minimum wire size = 12 AWG
- Inputs: Wire sizes: AWG (US); Conductor: Copper; Circuit: Single-phase / DC; Supply voltage: 250 V; Load current: 22 A; One-way cable length: 33 m; Maximum voltage drop: 3%.
- Formula: Smallest size with 2 I R L ÷ V ≤ limit (and ampacity ≥ I)
- Result: Minimum wire size = 12 AWG
Things to keep in mind
- Ampacity derating for bundling, temperature and conduit fill isn't applied. A licensed electrician must verify any installation.
Questions people ask
Why is 14 AWG limited to 15 A?
NEC 240.4(D) caps overcurrent protection for small conductors.
Copper or aluminium?
Aluminium needs about two sizes larger for the same current.